Bunsen 13mm (1/2) Nickel Plated with Safety Cutout- F4006/1TC

OVERALL HEIGHT: 145 mm
O.D. OF INLET: 9.25 mm
I.D. OF OUTLET: 9.0 mm
Typical gas consumption 144 litres per hour

These burners are supplied with a flame failure device that shuts off the gas supply to the burner within approximately 20 seconds of the flame being extinguished.

The safety features are all contained within the burner – an electrical supply from either mains or battery is therefore not required.

The moving parts, ie. The actuator and thermocouple can be replaced, although exhaustive tests have not yet caused a failure.

However, in the event of damage, we recommend that repairs are carried out in our factory to ensure that the burner is properly adjusted and operates correctly.

Our LPG burners are designed to work at propane 35 millibars (14 inches water gauge) on butane (Calor) 28 millibars (11 inches water gauge) with the appropriate pressure reduction valves being fitted to the gas cylinders.

Liquid Petroleum Gases are much more searching than either coal or natural gas, for this reason all the jets on LPG are sealed with a jointing compound.

In the event that jets might be changed a jointing compound must be used.

All burners are constructed utilising a heavy pressure diecast base painted in a blue chemically resistant acrylic finish.

All burners are tested for flame quality and leakage prior to packing.

The tests are carried out at the standard gas pressure for each specific type gas.

In the event that jets might be changed a jointing compound must be used.

We cannot accept liability resulting from burners that have been stripped for whatever reason.

Weight 0.45 kg

Get a Quote